Skip to main navigation Skip to search Skip to main content

Upstream Boundary Element Method for Calculating the Ionized Field of the High Voltage Direct Current Conductor

  • North China Electric Power University

Research output: Contribution to journalArticlepeer-review

Abstract

Ionized field strength on the ground level is one of the fundamental electromagnetic environment parameters of ultrahigh voltage direct current (UHVdc) transmission lines. An algorithm of an upstream boundary element method is presented in this paper to calculate the ionized field on the boundary with a high accuracy. The ionized field is generated and measured in an experimental platform with an HV conductor to a grounded cylindrical corona cage. The relations between ionized field strength and applied voltage, conductor position, and conductor diameter are investigated. Calculations show that the relative error of the ionized field on the HV electrode could be reduced to 0.1% when compared with the analytical solution. Ionized field distribution under the typical ±1100 kV UHVdc transmission lines is also analyzed as the application.

Original languageEnglish
Article number7582505
Pages (from-to)2424-2431
Number of pages8
JournalIEEE Transactions on Power Delivery
Volume32
Issue number6
DOIs
StatePublished - Dec 2017
Externally publishedYes

Keywords

  • Boundary element method
  • HVDC
  • corona discharge
  • field mill
  • ionized field
  • upstream element

Fingerprint

Dive into the research topics of 'Upstream Boundary Element Method for Calculating the Ionized Field of the High Voltage Direct Current Conductor'. Together they form a unique fingerprint.