Synchrophasor measurement-based fault location technique for multi-terminal multisection non-homogeneous transmission lines

  • Ting Wu*
  • , Chi Yung Chung
  • , Innocent Kamwa
  • , Jiayong Li
  • , Mingwen Qin
  • *Corresponding author for this work
  • Hong Kong Polytechnic University
  • University of Saskatchewan
  • Hydro-Quebec

Research output: Contribution to journalArticlepeer-review

Abstract

This study presents a fault-location technique for multi-terminal multi-section non-homogeneous transmission lines which combine overhead lines with underground power cables, by using voltage and current synchrophasors obtained from phasor measurement units. First, a faulty line branch is selected to narrow down the suspected faulty area. Then, the faulty section and the exact fault location can be identified by calculating the normalised fault distance for each section on the selected faulty branch. Computational burden of the proposed analytical scheme is very low because it avoids iterative computations. Promising simulation results show that the proposed fault location technique can accurately locate the fault regardless of the fault type, fault resistance, fault location, pre-fault loading and line parameters inaccuracies.

Original languageEnglish
Pages (from-to)1815-1824
Number of pages10
JournalIET Generation, Transmission and Distribution
Volume10
Issue number8
DOIs
StatePublished - 19 May 2016
Externally publishedYes

Fingerprint

Dive into the research topics of 'Synchrophasor measurement-based fault location technique for multi-terminal multisection non-homogeneous transmission lines'. Together they form a unique fingerprint.

Cite this