Skip to main navigation Skip to search Skip to main content

Study on arc behaviors at opening a 270v resistive circuit by bridge-type contacts under magnetic field

  • School of Electrical Engineering and Automation, Harbin Institute of Technology

Research output: Contribution to journalArticlepeer-review

Abstract

Bridge-type contacts are mainly used in high voltage direct current contactors for their performance of arc extinguishment and break capacity. It is also easy to add external magnetic field in them to blow the arc. Experiments on the arc behaviors were carried out when a copper bridge-type contact pair opening a 270V resistive circuit in the air. Influences of the shape of the movable contact, the opening speed and the magnetic flux density on the key behaviors, such as the arc duration, the arc re-ignition and the stability of arcing process, were investigated by using an oscilloscope and a high-speed camera. It was revealed that a uniform magnetic field with proper density could extinguish the arc stably and could reduce the arc re-ignition.

Original languageEnglish
Pages (from-to)1124-1131
Number of pages8
JournalIEICE Transactions on Electronics
VolumeE96-C
Issue number9
DOIs
StatePublished - Sep 2013
Externally publishedYes

Keywords

  • Arc behaviors
  • Bridge-type contacts
  • Copper contacts
  • Dc arcs

Fingerprint

Dive into the research topics of 'Study on arc behaviors at opening a 270v resistive circuit by bridge-type contacts under magnetic field'. Together they form a unique fingerprint.

Cite this