Abstract

To investigate the influence of the dynamic coupling effect (DCE) on the failure of 1000-kV outgoing line frame (OLF1000) subjected to real strong earthquakes, a reduced-scale experiment was performed on a shaking table. The transmission lines were simulated by the massless springs with dynamic stiffnesses. The numerical recurrence of the experiment was carried out in the finite element software and the results obtained by the experimental and numerical recurrence matched very well. The collapse analysis of OLF1000 was conducted by FEM. The research results significantly indicate that the DCE between the transmission lines and OLF1000 is very strong. It obviously reduces the seismic responses of OLF1000 under small earthquakes, accelerates the development of the existed damage of OLF1000 under strong earthquakes and apparently reduces the ultimate bearing capacity of OLF1000.

Original languageEnglish
Title of host publicationIASS Symposium 2019 - 60th Anniversary Symposium of the International Association for Shell and Spatial Structures; Structural Membranes 2019 - 9th International Conference on Textile Composites and Inflatable Structures, FORM and FORCE
EditorsCarlos Lazaro, Kai-Uwe Bletzinger, Eugenio Onate
PublisherInternational Center for Numerical Methods in Engineering
Pages2464-2471
Number of pages8
ISBN (Electronic)9788412110104
StatePublished - 2019
EventIASS Symposium 2019 - 60th Anniversary Symposium of the International Association for Shell and Spatial Structures; Structural Membranes 2019 - 9th International Conference on Textile Composites and Inflatable Structures, FORM and FORCE - Barcelona, Spain
Duration: 7 Oct 201910 Oct 2019

Publication series

NameIASS Symposium 2019 - 60th Anniversary Symposium of the International Association for Shell and Spatial Structures; Structural Membranes 2019 - 9th International Conference on Textile Composites and Inflatable Structures, FORM and FORCE

Conference

ConferenceIASS Symposium 2019 - 60th Anniversary Symposium of the International Association for Shell and Spatial Structures; Structural Membranes 2019 - 9th International Conference on Textile Composites and Inflatable Structures, FORM and FORCE
Country/TerritorySpain
CityBarcelona
Period7/10/1910/10/19

Keywords

  • 1000-kV outgoing frame
  • Collapse analysis
  • Dynamic coupling effect
  • Failure mechanism
  • Shaking table test