Abstract
The peak shaving parameter limit is important to the choice of heating system capability, and is relate to heat load distributing and economic question. The percentage of shaving peak heat source and optimizes operating flux in maximal heat pump load were analyzed, the radiator was took as end heater apparatus in the heat steady condition and the work temperature was developed for shaving heating peak load, through analyzing the temperatures of radiator supply and discharge hot water and the function relationship between system flux and outside air temperature. The flux temperature limit was brought forward and defined. Key design parameter was analyzed, system capability and heat load distributing. Result show that flux is in the extreme, the flux temperature limit is dividing point and maximal peak shaving load percentage is fifty percents.
| Original language | English |
|---|---|
| Pages (from-to) | 79-82 |
| Number of pages | 4 |
| Journal | Journal of Hunan University of Science and Technology |
| Volume | 20 |
| Issue number | 1 |
| State | Published - Mar 2005 |
Keywords
- Heat pump heat source
- Operating flux
- Peak heating
- Percentage of heat load
- Temperature dividing point
Fingerprint
Dive into the research topics of 'Parameter limit and heat load distributing of heat pump peak shaving heating in frosty district'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver