Optimum design of interphase reactor with double-tap changer applied to multipulse diode rectifier

  • School of Electrical Engineering and Automation, Harbin Institute of Technology

Research output: Contribution to journalArticlepeer-review

Abstract

In this paper, the optimum turns ratio of an interphase reactor (IPR) with a double-tap changer is presented with mathematical analysis. The relation between the total harmonic distortion (THD) of the input current and the turns ratio is introduced, and based on the relation, the optimum turns ratio when the THD is minimal is obtained. Via another relation between the ripple coefficients of the output voltage and the turns ratio, the optimum turns ratio is derived when the ripple coefficient is minimal. Meanwhile, using the optimum turns ratio, a new formula to calculate the critical value of IPR is written. Some computer simulation results and experiments are included to support the theoretical analysis of optimum design.

Original languageEnglish
Article number5371863
Pages (from-to)3022-3029
Number of pages8
JournalIEEE Transactions on Industrial Electronics
Volume57
Issue number9
DOIs
StatePublished - Sep 2010
Externally publishedYes

Keywords

  • Double-tap changer
  • interphase reactor (IPR)
  • multipulse rectifier
  • optimum turns ratio