Skip to main navigation Skip to search Skip to main content

Numerical Analysis of the Effect of Converter Transformer Combined Magnetic Shielding on Stray Load Losses Considering DC Bias

  • Haoming Wang
  • , Qingxin Yang*
  • , Yang Li
  • , Yongjian Li
  • , Yue Zhang
  • , Jianmin Wang
  • *Corresponding author for this work
  • Hebei University of Technology
  • Baoding Tianwei Baobian Electric Co. Ltd.

Research output: Contribution to journalArticlepeer-review

Abstract

In order to accurately analyze the effect of combined magnetic shielding on stray load losses of converter transformer, a three-dimensional (3D) finite-element analysis (FEA) model is established. The total losses can be gotten by summing the simulated losses of each harmonic. The effectiveness of the presented simulation method is verified by comparing the simulated and tested stray load losses of the converter transformer in the case of rated operation without lobe-type magnetic shielding structure. Afterwards, the installation position of lobe-type magnetic shielding is optimized by considering its effect on stray load losses. Finally, the stray load losses under different DC bias currents are simulated and analyzed.

Original languageEnglish
Article number9462454
JournalIEEE Transactions on Applied Superconductivity
Volume31
Issue number8
DOIs
StatePublished - Nov 2021
Externally publishedYes

Keywords

  • DC bias
  • Magnetic shielding
  • converter transformer
  • stray load losses

Fingerprint

Dive into the research topics of 'Numerical Analysis of the Effect of Converter Transformer Combined Magnetic Shielding on Stray Load Losses Considering DC Bias'. Together they form a unique fingerprint.

Cite this