Abstract
For unbalanced three-phase grid voltage, the traditional Virtual Synchronous Generator (VSG) control cannot overcome the distortion of output current. For this reason, a new control method is proposed in this study. The additional positive-sequence current adjuster to the traditional VSG control allows the reference current to track the positive-sequence current, and inhibit the negative-sequence components. Meanwhile, the oscillations in the power system are decreased. The proposed method has been simulated using Matlab/Simulink and verified experimentally on actual platform. The reliability and effectiveness of the proposed control method have also been compared with the traditional VSG control.
| Original language | English |
|---|---|
| Pages (from-to) | 165-170 |
| Number of pages | 6 |
| Journal | IET Renewable Power Generation |
| Volume | 13 |
| Issue number | 1 |
| DOIs | |
| State | Published - 7 Jan 2019 |