The hydrodynamic calculation method in use is the "hydrodynamic calculation method for hot water boiler". The disadvantage of this method is that it is hard to ascertain the working medium flux of each tube and furthermore, the working point is inaccurate. To overcome the inaccurateness, a numerical hydrodynamic calculation method called hydrodynamic loop analysis method or loop analysis method was investigated. It took those factors affecting the flux of each tube into account and obtained the accurate flux of the working medium in each tube under the condition that the heat load, the parameter of structure and the flow resistance coefficient of each tube were supplied. The hydrodynamic characteristic of a single loop was researched by both the general method and the loop analysis method under the same parameters to demonstrate the correctness of the hydrodynamic loop analysis method. Then the hydrodynamic characteristic of a hot water boiler with natural circulation was calculated and analyzed by the hydrodynamic loop analysis method as well as the general one. Results show that hydrodynamic loop analysis method is more accurate and acceptable.

Original languageEnglish
Pages (from-to)66-70
Number of pages5
JournalZhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering
Volume30
Issue number5
StatePublished - 15 Feb 2010
Externally publishedYes

Keywords

  • Hydrodynamic
  • Loop analysis method
  • Water boiler

Fingerprint

Dive into the research topics of 'Hydrodynamic loop analysis method for hot water boiler with natural circulation'. Together they form a unique fingerprint.

Cite this