Field measurement and analysis of heat rejection from air-conditioning refrigeration system of office building in urban

  • Kang Mu*
  • , Jing Liu
  • , Zhen Lu
  • , Yong Cao
  • , Jian Li Zhang
  • *Corresponding author for this work
  • Harbin Institute of Technology
  • Shenzhen Institute of Building Research Co., Ltd.
  • China Academy of Building Research

Research output: Contribution to journalArticlepeer-review

Abstract

To study the heat rejection law of office building air-conditioning refrigeration system with a large heat rejection per unit building area, one office building in Shenzhen and three office buildings in Beijing in the center of the city were selected as the main research objects, and the heat rejection from air-conditioning refrigeration system through cooling tower was discussed in two forms: sensible heat and latent heat in the field measurement method. This field study results show that the total heat rejection from building air-conditioning refrigeration system per unit building area has a daily average value in the range of 85~106 W/m2, where the sensible and latent heat share the proportion of 1%~5% and 95%~98.85% respectively. It indicates that office building air-conditioning refrigeration system releasing the condensing heat into the outdoor environment through cooling tower is mainly in the form of latent heat, which has a significant effect on the building surrounding humidity environment. Finally, higher temperature and humid outdoor climatic conditions are not conducive to the heat and moisture rejection from the building air-conditioning refrigeration system.

Original languageEnglish
Pages (from-to)125-132
Number of pages8
JournalHunan Daxue Xuebao/Journal of Hunan University Natural Sciences
Volume42
Issue number11
StatePublished - 25 Nov 2015

Keywords

  • Air-conditioning refrigeration system
  • Field measurement
  • Latent heat rejection
  • Office building
  • Sensible heat rejection

Fingerprint

Dive into the research topics of 'Field measurement and analysis of heat rejection from air-conditioning refrigeration system of office building in urban'. Together they form a unique fingerprint.

Cite this