Skip to main navigation Skip to search Skip to main content

Experiments on improvements in space heating performance of the triple-sleeve energy exchanger based energy storage heat pump

  • Harbin Institute of Technology

Research output: Contribution to journalArticlepeer-review

Abstract

To enhance the heating performance of the air source heat pump (ASHP) system in the low ambient temperature surroundings, the triple-sleeve energy exchanger (TRESE) for space heating mode was proposed. The running stability and the coefficient of performance (COP) of the energy storage heat pump system (ESHP) in the TRESE heating mode, the TRESE combined ASHP system heating mode, and the solar hot water assisting TRESE heating mode, were compared and discussed. The results demonstrate the substantial advance in the heating performance of the ESHP system in the TRESE heating mode and the ASHP system heating mode. For instance, when the temperature and volume flow of the solar hot water are 28℃ and 300 L/h, respectively, the evaporating temperature and COP achieves -2.8℃ and 2.8 respectively.

Original languageEnglish
Pages (from-to)121-127
Number of pages7
JournalHunan Daxue Xuebao/Journal of Hunan University Natural Sciences
Volume42
Issue number7
StatePublished - 25 Jul 2015

Keywords

  • Heating COP
  • Performance during the low ambient temperature surroundings
  • Triple-sleeve energy exchanger

Fingerprint

Dive into the research topics of 'Experiments on improvements in space heating performance of the triple-sleeve energy exchanger based energy storage heat pump'. Together they form a unique fingerprint.

Cite this