Abstract

Because it is necessary to know the influence of groundwater advection on performance of vertical geothermal heat exchanger (GHE), coupled heat conduction and advection experiments on soil were implemented. These experiments referred to the influence of GHE heat load in saturated soil without seepage on the temperature contour of surrounding soil, and the influence of groundwater flowrate, initial soil temperature, and GHE heat load in soil with seepage on temperature field of soil, respectively. The experimental result shows when the ground source heat pump (GSHP) system is used in the zone with hot summer and cold winter, or sub-tropical zone, it is better to adopt GSHP-cooling tower hybrid system, or bury the GHE in zone with high groundwater flowrate for system's long term efficient operation.

Original languageEnglish
Pages (from-to)874-880
Number of pages7
JournalTaiyangneng Xuebao/Acta Energiae Solaris Sinica
Volume28
Issue number8
StatePublished - Aug 2007

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy

Keywords

  • Experimental research
  • Geothermal heat exchanger
  • Groundwater flow

Fingerprint

Dive into the research topics of 'Experimental research on influence of groundwater advection on performance of GHE'. Together they form a unique fingerprint.

Cite this