Skip to main navigation Skip to search Skip to main content

超大型冷却塔风荷载时程响应及动力抗风性能分析

Translated title of the contribution: Analysis of wind pressure time-history response and wind resisting performance for super large cooling tower
  • School of Civil Engineering, Harbin Institute of Technology
  • Northwest Electric Power Design Institute Co., Ltd.

Research output: Contribution to journalArticlepeer-review

Abstract

Wind tunnel tests and an artificial generation method were used to measure the wind pressure time-history response of a 220 m-high super large cooling tower, and a structural model is established based on the domestic standard and eigenvalue buckling. Finally, the finite element method was used to analyze the wind load dynamic wind resistance characteristics. The analysis results indicate that the response of artificial wind pressure is larger than that of wind tunnel tests. The overall displacement and each layer stress of the extracted unit by the artificial generation method have a large fluctuation. Under the action of dynamic wind loading, the maximum deformation of the structure is located in the throat of the windward tower, and the maximum stress is located in the lower part of the windward tower. The results can provide a reference for the revision of the surface wind load of the super-large cooling tower and relevant technical specifications.

Translated title of the contributionAnalysis of wind pressure time-history response and wind resisting performance for super large cooling tower
Original languageChinese (Traditional)
Pages (from-to)118-124
Number of pages7
JournalGongcheng Lixue/Engineering Mechanics
Volume36
DOIs
StatePublished - Jun 2019

Fingerprint

Dive into the research topics of 'Analysis of wind pressure time-history response and wind resisting performance for super large cooling tower'. Together they form a unique fingerprint.

Cite this