Abstract
Through the sensitivity analysis, the parameters which have great influence on the random seismic response of the main transformer are found, which can provide reference for seismic design and subsequent seismic vulnerability analysis. In this paper, based on SAP2000, the finite element model of the main transformer is constructed and the seismic response is calculated. The sensitivity of the parameters is analyzed by mutual information method and partial rank correlation method respectively. The results show that the order of sensitivity of the parameters obtained by the two methods is the same, PGA is the most influential parameter on the random seismic response of the main transformer, and the length of high voltage bushing Hl, density of high voltage bushing Dc, equivalent stiffness coefficient of flange section Fr, intrinsic weight Bw and input direction also have a certain influence, while other parameters have little influence on the random seismic response of the main transformer.
| Translated title of the contribution | Sensitivity analysis of random seismic response of main transformer in substation |
|---|---|
| Original language | Chinese (Traditional) |
| Pages (from-to) | 414-422 |
| Number of pages | 9 |
| Journal | Yingyong Lixue Xuebao/Chinese Journal of Applied Mechanics |
| Volume | 40 |
| Issue number | 2 |
| DOIs | |
| State | Published - Apr 2023 |
| Externally published | Yes |
Fingerprint
Dive into the research topics of 'Sensitivity analysis of random seismic response of main transformer in substation'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver