Abstract
As the hub of power system,the seismic performance evaluation of substation is particularly important,and the tank circuit breaker coupling system is one of the important equipment in substation.In order to study the seismic performance of 750 kV-SF6tank circuit breaker coupling system,incremental dynamic analysis(IDA)and probabilistic seismic demand model(PSDM)were used to evaluate its seismic vulnerability.Firstly,the structural characteristics and seismic loss characteristics of 750 kV-SF6tank circuit breaker coupling system are analyzed,and the finite element model is constructed.Based on the incremental dynamic analysis(IDA),the peak ground acceleration(PGA)is used as the input parameter to obtain the seismic response of the key vulnerable parts.On this basis,the seismic vulnerability curves of each vulnerable part under different seismic damage states are generated by probabilistic seismic demand model(PSDM).Finally,based on the reliability theory,the seismic vulnerability model of 750 kV-SF6can circuit breaker coupling system is obtained.The results show that when PGA reaches 0.6g,the failure probability of 750 kV-SF6tank circuit breaker coupling system is 0%,1%~5%,88%~93% and 100%,respectively.
| Translated title of the contribution | Seismic vulnerability model of 750 kV-SF6tank circuit breaker coupling system based on probabilistic seismic demand analysis |
|---|---|
| Original language | Chinese (Traditional) |
| Pages (from-to) | 832-839 |
| Number of pages | 8 |
| Journal | Yingyong Lixue Xuebao/Chinese Journal of Applied Mechanics |
| Volume | 40 |
| Issue number | 4 |
| DOIs | |
| State | Published - Aug 2023 |
| Externally published | Yes |
Fingerprint
Dive into the research topics of 'Seismic vulnerability model of 750 kV-SF6tank circuit breaker coupling system based on probabilistic seismic demand analysis'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver